Egypt Zones accountACCOUNT
Supply of Biocide - Algaecide
Chemicals
Reference 1613/2011
Date 3/1/2011
Location Middle East
Scope Purchasing specifications of Biocide - Algaecide. Bactericide for industrial cooling water

- Should be compatible with all corrosion, scale prevention and chlorination programmes for cooling water systems.

- Should control and prevent the growth of algae, fungi and both aerobic, anaerobic and sulphate reducing bacteria in cooling water.

- Should work as a biocide and bio –dispersant for effective

- Should be effective under alkaine conditions

- (ph range 7.5-9.0).

- It should be biodegradable.

- Dosing rate to be defined.

- Shelf life of products to be given.

- It should not contain heavy metals or phenols.

- It should have been field tested successfully in our plants.

- Lab procedures and necessary chemical reagents and apparatus

For determining bacteria counts of all kinds in the samples must be offered.

QTY-:35 ton

Bio Dispersant Specification:-

1. Strong dispersent affects gives outstanding slime exfoltating efficiency, evenly effective exfoltating all acidic to alkali phase.

2. Long period of stability and sustained effectiveness even if in relatively high temperature.

3. Neither contains heavy metals nor use inter materials.

4. Shelf life of product to be given.

5. It must have been filed tested successfully in our facilities.

6. Lab. procedures & necessary chemical reagents & apparatus for general testing & evaluation of water samples & determining residual of the product in the samples must be offered.

QTY-: 25 ton

Purchasing specifications of corrosion and scale inhibitor for circulating cooling water systems

1- Organic ploymer, not contain zinc or any other material.

2- It must be biodegranable and compatible with the raw and make – up water characteristics.

3- It must be non-chromate type.

4- It must be resistent to time temperature and ph

5- It must provide a low corrision rate (5 mpy) max.

6- It should eliminate h2so4 injection.

7- It should be restent to chlorin.

8- Protection from corrosin should include copper and copper alloys.

9- Minimum in-plant shelf life must be stated.

10- Type and concentrations of active ingredients must be stated.

11- It must have been field tested successfully in our facilities.

12- Lab procedures and necessary chemical regents apparatus for general testing and evaluation of water samples and for determining residual of the product in the samples must be offered.

Note:

Measurement devices with the reagent should be provide as below:-

- Spectrophotometer.
- Ph meter
- Conductivity meter.
- Chlorine meter.

QTY-: 140 TON

Coling tower specification

Chemical analysis

- PH / range 8.1 - 8.5

- Conductivity / range 1100 - 2430 ΅S/CM

- TDS / range 720 – 2000 PPM

- M -ALK / range 140 – 274 PPM

- CAH / range 236 – 284 PPM

- TH / range 400 – 700 PPM

- Turbidity / range 6 – 12 NTU

- N.C / range 1.1 – 2.1

- Free chlorine / range 0.0 – 0.5 PPM

System specification:-

- Holding volume m3 - light oil (10000) / lube – 1 (230) / lube - 2 (1450) / lube – 3 (2700)

- Recirculation rate m3/hr - light oil (16000) / lube – 1 (1135) / lube – 2 (2460) / lube – 3 (5400)

- Blow down m3/hr - light oil (170) / lube – 1 (30) / lube - 2 (150) / lube – 3 (50)

- Make up m3 /hr - light oil (400) / lube – 1 (38.1) / lube - 2 (176) / lube – 3 (120)

- Chemical consumption for four cooling towers should be mentioned as kg/ day for worst conditions.

- Corrosion rate should be limited to less than 5mpy .

Bidding Information

Bid Bond 1% from submitted prices
Documents Price ID 150 000
Chemicals
Related Prooducts: Chemicals General
Related Tenders: General

Related Articles

For Buyers
Advertise your Purchasing Requests

For Suppliers
Promote your Products
Egypt Zones
Copyright © Universal Solutions All rights reserved. - Privacy Policy.