Reference | SGC-M101-2011 |
Date | 8/25/2011 |
Location | Middle East |
Scope | - # 12 Flame arresters to be used in gas compression stations installed Horizontaly into pipes conveying condensations to the burning pit at (15-20)m of distance from burning point starting igintion located inside The burning pit,detonation cylindrical type, two pieces with circular flame Barrier element inserted between two bolted flanges. Specifications: - Pressure drop: (1) psi max. Design pr: (400) psig. Operation temp: 55°C, Inconsidrable flowrate (low and interval) material of barrier elements: AISI 316orAISI304.flanged ends according to ANSI/ B16.5: (4)” class 300. Explosion group (EU: IIA, US: D). two barrier elements to be equipped as Spare parts with each flame arrestor. - # 1 As in item (1) but (10)” class 300. - Country of origin: USA, UK, Italy, France, Canada, Holland. - Third party test & origin certificates are required. |
Bid Bond | 1% from Submitted Prices |