Reference | BID9150 |
Date | 9/15/2009 |
Location | Middle East |
Scope | Ref. No.: BD/F/16/2009 Issue Date: 15/09/2009 Pre-Tender Meeting Date: 27/09//2009 Bid Closing Date: 06/10/2009 Bid Bond: 1% From the total value of tender price Fee: 100 USD Scope of Work: Supplying download meters size (2.5) as the following meters specifications: - Used to count download quantity. - Inlet threaded with male BS (2.5) inch. - The system must contain (filter, air separator, strainer and isolate valve). - Amp. Temp. range (-5, 60)° C. - The system should be operate at hazardous zone in fuel station near un loading points. - The meters operate on (24 vdc, 220 vac, 50 hz). - (Flammable & explosion) proof. 1- Supplying download meters as following: a- # 50 meter for gasoline - Temp range of product (-5, 60)° C - Specific gravity at 15.6° C (0.770 - 0.775) - Sulfur content (% w): 0.05 b- # 182 meter for gas oil - Temp range of product (-5, 60)° C - Specific gravity at 15.6° C (0.85) - Viscosity cst at 40° C: 5.6 - Sulfur content (% w): (1) max c- # 332 meter for kerosene - Temp range of product (-5, 60)° C - Specific gravity at 15.6° C (0.801) - Sulfur content (% w): (2) max 2- Calibration unit as the following: a- # 29 master meter to Calibrate gasoline meter: - Temp range of product (-5, 60)° C - Specific gravity at 15.6° C (0.770 - 0.775) - Sulfur content (% w): 0.05 b- # 10 meter for gas oil meter: - Temp range of product (-5, 60)° C - Specific gravity at 15.6° C (0.85) - Viscosity cst at 40° C: 5.6 - Sulfur content (% w): (1) max c- # 34 meter for kerosene meter: - Temp range of product (-5, 60)° C - Specific gravity at 15.6° C (0.801) - Sulfur content (% w): (2) max. Origin must be: USA, Germany, France, Swiss, Italy or Japan. |